CVE-2023-25915: Danfoss AK-SM 800A RCE
Active exploitation confirmed in CISA KEV.
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:HActive exploitation confirmed in the wild. CISA added this to the KEV catalog on 2026-11-25. Federal agencies must patch by 2026-11-28.
TL;DR - CVE-2023-25915 is an authenticated remote command-execution vulnerability in Danfoss AK-SM 800A software before version 3.3. - CISA added it to the Known Exploited Vulnerabilities catalog on November 25, 2026. - Upgrade to version 3.3 or the latest supported release, restrict access, and investigate affected controllers.
CVE-2023-25915 affects Danfoss AK-SM 800A systems running software below version 3.3. The vulnerability enables authenticated remote command execution and is especially important for organizations responsible for commercial refrigeration, facilities management, and industrial control system security.
Are You Affected?
CVE-2023-25915 affects Danfoss AK-SM 800A Series systems running software below version 3.3. These controllers are used in commercial refrigeration and facility-management environments, where compromise can affect both the device and connected operational networks.
The vulnerability requires an authenticated account, but it is remotely reachable and does not require victim interaction. Treat any controller exposed to the internet, reachable from an untrusted network, or managed with weakly controlled credentials as high risk.
| Field | Details |
|---|---|
| CVE ID | CVE-2023-25915 |
| Product | Danfoss AK-SM 800A Series, also referenced as AK-SM800A |
| Affected versions | Software versions below 3.3 |
| Fixed version | Version 3.3, or the latest supported release supplied by Danfoss |
| Vulnerability type | Improper Input Validation, CWE-20 |
| Impact | Authenticated remote command execution |
| CVSS | NVD: 8.8 High; CNA/DIVD: 9.9 Critical; Danfoss: 9.8 Critical |
| Attack vector | Network |
| Authentication or privileges required | Low privileges or an authenticated account is required |
| User interaction | None |
| Patch available | Yes |
| CISA KEV status | Yes, added November 25, 2026 |
| KEV remediation due date | November 28, 2026 |
Version reporting requires care. Danfoss and DIVD describe systems below 3.3 as affected, while NVD’s CPE data may represent the range differently. For operational purposes, treat version 3.3 as the minimum fixed release, then confirm the exact installed version and upgrade path with Danfoss.
Inventory teams should identify every AK-SM 800A controller, including systems managed by contractors or facilities vendors. Do not limit the search to devices with public IP addresses. An attacker who compromises another host on a building-management or operational-technology network may be able to reach an internally exposed controller.
Analyst’s Take: The immediate priority is version validation and network containment, not exploit reproduction. KEV inclusion and the November 28, 2026 remediation due date justify treating every unverified controller as potentially vulnerable while its version and access paths are checked.
The Fix, If You’re in a Hurry
Upgrade affected AK-SM 800A systems to software version 3.3 or the latest supported version provided through Danfoss’s AK-SM 800A support channel. Danfoss identifies software version 3.3 as the remediation for this vulnerability set. Before upgrading, confirm compatibility, maintenance requirements, and the correct package with Danfoss or the authorized support organization.
CISA added this CVE to the KEV catalog on November 25, 2026, with a remediation due date of November 28, 2026. Covered organizations should follow applicable CISA requirements and internal critical-vulnerability procedures. KEV inclusion supports prioritizing both remediation and compromise assessment.
If an immediate upgrade is not possible, reduce exposure until the controller can be patched. Remove direct internet access, restrict the management interface to trusted administration hosts, place the device in an appropriate network segment, and limit inbound access with firewall policy. Enforce unique credentials and review accounts with access to the controller. These controls reduce attack surface but do not correct the vulnerability.
Technical Notes: Upgrade and containment
Danfoss’s advisory recommends installing the patched software and does not specify a separate CVE-specific workaround. Because these are appliance-like operational systems, an upgrade may not be performed with a generic operating-system package manager. Use the vendor-provided update process rather than assuming a command such as apt upgrade or yum update is appropriate.
A practical change plan should include:
1. Record the controller model, current software version, and configuration backup.
2. Confirm the approved AK-SM 8000A software 3.3-or-later package with Danfoss.
3. Schedule the maintenance window with facilities and operations owners.
4. Restrict management access to approved administration hosts.
5. Apply the vendor update and verify the reported version.
6. Validate refrigeration, monitoring, alarms, integrations, and authentication.
7. Preserve pre- and post-upgrade logs for the incident-response record.
If patching must be deferred, implement an explicit allowlist at the network boundary. The exact syntax depends on the firewall platform, but the policy objective is to permit management only from named, trusted hosts:
ALLOW <trusted-management-subnet> -> <AK-SM-8000A> <documented-management-service>
DENY ANY -> <AK-SM-8000A> <management-service>
DENY <AK-SM-8000A> -> ANY <unnecessary-egress>
Do not expose the controller directly to the public internet while waiting for a maintenance window.
How This Vulnerability Works
CVE-2023-25915 is caused by improper input validation, classified as CWE-20. Danfoss describes the issue as allowing an authenticated remote attacker to execute arbitrary commands on the target system. In practical terms, data supplied through a remotely accessible AK-SM 800A function is not sufficiently constrained or safely handled before being processed by the underlying system.
The attacker must authenticate, but no additional user interaction is required. Once an attacker has a valid account and network access to the affected interface, malicious input may be processed as an operating-system command or otherwise reach command-execution functionality. The available public advisories do not provide a safe, complete exploit walkthrough, so defenders should not infer that the authentication requirement makes the issue low risk.
Successful command execution can give an attacker control over the controller’s processes, configuration, and locally accessible data. Depending on deployment architecture and network trust relationships, the device could also serve as a foothold for lateral movement into building-management, refrigeration, or broader operational-technology environments.
The precise vulnerable endpoint, parameter, and command-execution mechanism are not detailed in the cited primary sources. That limits exploit reproduction but does not reduce the remediation priority. Organizations should focus on version validation, access restriction, credential review, and evidence collection rather than attempting to reproduce exploitation on production controllers.
For background on related security terminology, see the glossary entries for what is RPO and what is FISMA.
Severity, Explained
The NVD CVSS 3.1 assessment is 8.8 High:
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
The vector indicates that exploitation is possible over the network (AV:N), requires no unusual conditions (AC:L), and requires low privileges or authentication (PR:L). No victim needs to click, approve, or otherwise interact with the attack (UI:N). The vulnerable component is assessed as having a high impact on confidentiality, integrity, and availability (C:H/I:H/A:H).
NVD’s score treats the impact scope as unchanged (S:U). CNA/DIVD published a 9.9 Critical assessment using:
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H
The S:C value means the consequences can extend beyond the vulnerable security authority. Danfoss reports a 9.8 Critical score. These differences reflect distinct scoring assessments, particularly around scope. They do not change the practical conclusion: an authenticated attacker may obtain command execution over a network, with potentially severe consequences for a controller that operates in an OT or facilities environment.
The authentication requirement is the main limiting factor in the score. It should not be mistaken for a meaningful defense if credentials are reused, exposed through another breach, granted broadly to contractors, or accessible from an internet-facing management interface.
Is It Being Exploited?
Yes. CISA added CVE-2023-25915 to its Known Exploited Vulnerabilities catalog on November 25, 2026. That listing confirms exploitation in the wild and makes this vulnerability a priority for organizations subject to applicable CISA remediation requirements.
CISA lists the known ransomware campaign use field as unknown. This means CISA has not associated the CVE with a known ransomware campaign in that catalog field; it does not mean exploitation is absent or harmless. Organizations should investigate affected assets even if they have no evidence of ransomware activity.
No verified public GitHub exploit repository was identified in the supplied source material. The absence of a public proof of concept should not be used to defer remediation. KEV status is stronger operational evidence than the absence of a public repository, and exploitation may involve privately held tooling, stolen credentials, or techniques that do not require a published exploit.
The vulnerability requires authentication, so incident responders should examine how credentials could have been obtained. Relevant possibilities include password reuse, exposed remote-access systems, compromised vendor accounts, excessive contractor access, and credential theft from hosts that can reach the controller.
Detecting It in Your Environment
Start with asset and version discovery. Use configuration-management records, facilities inventories, network scans, DHCP data, switch tables, and vendor-management records to identify AK-SM 800A systems. Validate the installed software version through the controller’s supported administrative interface or Danfoss-approved process. A device that cannot be version-validated should be treated as potentially vulnerable until its status is confirmed.
Next, review authentication and web-access telemetry around each affected controller. Look for successful logins from unusual source addresses, authentication attempts outside normal maintenance windows, newly created or rarely used accounts, bursts of failed logins followed by success, and requests containing unexpected shell metacharacters or command-like values. The exact log field names and endpoint paths vary by software version and deployment, so avoid treating the examples below as a vendor-specific signature.
Technical Notes: Detection queries and log patterns
A generic SIEM query can identify suspicious authentication activity near vulnerable assets:
device_product = "Danfoss AK-SM 800A"
AND (
event_type IN ("authentication_success", "authentication_failure", "web_request")
OR message MATCHES "(?i)(cmd|command|shell|/bin/sh|powershell|;|\\||&&|\\$\\()"
)
| stats count,
values(src_ip) as source_addresses,
values(username) as accounts,
min(timestamp) as first_seen,
max(timestamp) as last_seen
by device_ip, event_type
| where count >= 1
This is a starting point, not a validated exploit signature. Tune it against normal administrative traffic and confirm field mappings in the actual product logs. Command-like strings may produce false positives, while a capable attacker may use encoding or other input forms that do not match the pattern.
At the network level, alert on management-interface connections from outside approved administrative subnets:
alert when
destination_asset = "AK-SM-800A"
AND destination_port IN (<documented-management-ports>)
AND source_ip NOT IN <approved-management-subnets>
Review outbound connections from the controller as well. Unexpected DNS queries, connections to unfamiliar internet addresses, new internal peer communication, or traffic beginning immediately after a suspicious login may indicate post-exploitation activity. Preserve firewall, authentication, web, DNS, and network-flow logs before rotating or overwriting them.
If compromise is suspected, isolate the controller in coordination with facilities and operations personnel. Do not make uncoordinated changes that could disrupt refrigeration, alarms, or safety-related processes. Preserve evidence, rotate credentials that could have accessed the device, and involve Danfoss or the relevant incident-response team.
References and Further Reading
The primary technical and remediation references are the Danfoss advisory and the coordinated-disclosure records. Danfoss identifies the affected product and fixed software level, while DIVD provides additional vulnerability-record context. The NVD record consolidates vulnerability metadata and CVSS assessments.
CISA’s KEV catalog is especially important for prioritization because it records confirmed exploitation and provides the remediation deadline. The ransomware field being unknown should be read narrowly and should not override the confirmed exploitation status.
- NVD: CVE-2023-25915
- Danfoss Security Advisory DSA-2023-08-01
- DIVD CVE record: CVE-2023-25915
- DIVD case record: DIVD-2023-00025
- CISA Known Exploited Vulnerabilities catalog
CVE-2023-25915 should be handled as an urgent OT and facilities-security issue. Start by confirming versions and removing unnecessary network exposure, then review account access and conduct a compromise assessment before closing the remediation task.